Freight Dual Holeless

(Click images to enlarge)

The design utilizes two hydraulic single stage jacks, located on each side of the platform and installed directly on the pit floor.

Advantages:

  • Jack hole is not required. Eliminating the cost of drilling and the risk of ground contamination from oil leak.
  • Offered in both low and high capacity elevators.
  • Accommodates front and rear opening configurations.




Disadvantages:

  • May require a larger hoistway width to accommodate jacks mounted on either side of the platform.
  • Limited to approximately 16’-0” of travel.
  • Side openings are not an option.
  • Material cost is typically higher when compared to an in-ground application.

Freight Dual Holeless Single Stage Hydraulic

Loading Capacity
(lbs)
Hoistway -
Width x
Depth
Platform -
Width x
Depth
Inside Cab
Width x
Depth

Door -
Width x
Depth

Front/
Rear
Pit
Depth
PDF AutoCAD
Class A 4000 9'-0" x 9'-4" 7-'0" x 8'-6" 6'-8" x 7'-11" 6'-8" x 7'-0" Front 4'-6" .pdf .dwg
4000 9'-0" x 9'-4" 7'-0 x 8'-6" 6'-8" x 7'-9" 6'-8" x 7'-0" Front/
Rear
4'-6" .pdf .dwg
5000 10'-2" x
9'-10"
8'-0" x 9'-0" 7'-8" x 8'-5" 7'-8" x 7'-0" Front 4'-6" .pdf .dwg
5000 10'-2" x
9'-10"
8'-0" x 9'-0" 7'-8" x 8'-3" 7'-8" x 7'-0" Front/
Rear
4'-6" .pdf .dwg
6000 10'-6" x
10'-10"
8'-4" x 10'-0" 8'-0" x 9'-5" 8'-0" x 7'-0" Front 4'-6" .pdf .dwg
6000 10'-6" x
10'-10"
8'-4" x 10'-0" 8'-0" x 9'-3" 8'-0" x 7'-0" Front/
Rear
4'-6" .pdf .dwg
8000 10'-8" x
12'-10"
8'-4" x 12'-0" 8'-0" x 11'-5" 8'-0" x 7'-0" Front 4'-6" .pdf .dwg
8000 10'-8" x
12'-10"
8′-4″ x 12′-0″ 8'-0" x 11'-3" 8'-0" x 7'-0" Front/
Rear
4'-6" .pdf .dwg
10000 12'-8" x
14'-10"
10′-4″ x 14′-0″ 10'-0" x 13'-5" 10'-0" x 7'-0" Front 4'-6" .pdf .dwg
10000 12'-8" x
14'-10"
10'-4" x 14'-0" 10'-0" x 13'-3" 10'-0" x 7'-0" Front/
Rear
4'-6" .pdf .dwg
Class B 8000 10'-10" x
22'-6"
8'-4" x 21'-8" 8'-0" x 21'-1" 8' x 8" Front 4'-6" .pdf .dwg
8000 10'-10" x
22'-6"
8'-4" x 21'-8" 8'-0" x 20'-11" 8' x 8" Front/
Rear
4'-6" .pdf .dwg
Class C 8000 10'-8" x
12'10"
8'-4" x 12'-0"
8'-0" x 11'-5" 8'-0" x 7'-0" Front 4'-6" .pdf .dwg
8000 10'-8" x
12'10"
8'-4" x 12'-0" 8'-0" x 11'-3" 8'-0" x 7'-0" Front/
Rear
4'-6" .pdf .dwg
10000 12'-8" x
14'10"
10'-4" x 14'-0" 10'-0" x 13'-5" 10'-0" x 7'-0" Front 4'-6" .pdf .dwg
10000 12'-8" x
14'10"
10'-4" x 14'-0" 10'-0" x 13'-3" 10'-0" x 7'-0" Front/
Rear
4'-6" .pdf .dwg

Additional Specs

  • Speed available to 150 FPM
  • Minimum Overhead = (Door Height x 1.5) + 9″