LSA 42.3
Leroy-Somer LSA 42.3 | 25 - 60 kVA
  • Přehled
  • Technické údaje
  • Doplňky
  • Ke stažení
Power 25 - 60 kVA*
Voltage 220 - 480V
Poles 4
Speed 1500 - 1800 rpm
Shaft height 180 mm
Max efficiency 94.1 %
 Excitation SHUNT / AREP / PMG
 Regulation  R220 / D350 / D550

* kVA/50Hz - kW/60Hz | Continuous / 40°C
(Discrepancies may occur, consult catalogue for exact figures)


Applications

Commercial application
Commercial
Industrial application
Industrial
Powerplant application
Powerplants
Marine application
Marine

Benefits

COMPACT
Optimized cooling system.

HIGH RELIABILITY
Class H insulation.

HIGH EFFICIENCY
Suited for prime applications 

Regulators R220 D350 D550
Mains Paralleling - -
3-phase sensing -
Advanced settings -
Data logging & monitoring -
Remote communication -
Remote voltage potentiometer -
CT for paralleling -
R791 RFI suppression kit (standard in Europe)

● : Included             ○ : Option             - : Not available


 

Flex plate / Flange 2 3 4
11 ½ -
10
8 -
7 ½ -

 


 

Insulation class H
Winding pitch 2/3 (wdg 6)
Number of wires 12
Protection IP 23
Altitude ≤ 1000 m
Overspeed 2250 rpm
Air flow 0.10m3/s, 50 Hz - 0.13m3/s, 60 Hz
Excitation system / AVR type

AREP / D350 or D550

SHUNT / R220

PMG / D350 or D550

Voltage regulation (Steady state) ± 0.25% AREP / ± 0.5 SHUNT
Short-circuit current (3 IN / 10 s) 300 % (3 IN) : 10s
  • Other voltages available (specific windings).
  • Space heater.
  • Winding protection for harsh environments and relative humidity above 95%.
  • Specific cable outlet.
  • Temperature detectors.
  • Thermal protection for winding and shields.
  • Remote Voltage Trimmer.
  • Filters on air inlet: derating 5%.
  • IP 44 Filters on air inlet and air outlet : derating 10%.
  • Lower shaft height on demand.
  • Two bearing.
  • Customizable Painting.